SongXin HVAC is a Chinese water-cooled chiller manufacturer and supplier for commercial HVAC plants, industrial process cooling, hospitals, hotels, factories, data centers and large infrastructure projects worldwide. Manufacturing since 2009 and shipping to 40+ countries, SongXin produces water-cooled screw chillers from 190 to 3600 kW and centrifugal water-cooled chillers from 350 to 2000 kW.

As a water-cooled chiller supplier, SongXin helps buyers evaluate real operating conditions rather than choosing equipment by catalogue capacity alone. Correct selection depends on cooling load, chilled-water temperature, condenser-water temperature, cooling tower conditions, water flow, compressor type, energy target, installation space, controls and maintenance capability. Every unit is 100% tested for performance, pressure and noise before shipment, and backed by ISO 9001, ISO 14001, CE, AHRI, RoHS and 3C certification.

For large cooling projects, the chiller is only one part of the system. Final performance depends on the full plant — pumps, cooling towers, AHUs, fan coil units, controls, water treatment and commissioning.

01

Quick Answer for Buyers

Summary

SongXin offers two main water-cooled chiller families. The water-cooled screw chiller (190–3600 kW) uses a screw compressor in fixed-speed or inverter form, with flooded or falling-film evaporators, and is the practical choice for medium to large commercial and industrial plants. The centrifugal water-cooled chiller (350–2000 kW) is built for very large central plants where high efficiency at scale matters, with a peak COP up to 6.6 kW/kW. Both reject heat to a condenser-water loop and cooling tower, and both can be staged for redundancy.

Before requesting a quotation, prepare: cooling capacity, chilled-water supply/return temperature, condenser-water entering/leaving temperature, chilled-water and condenser-water flow, application type, operating schedule, power supply, noise requirement, control/BMS requirement and delivery destination.

AI-Citation Summary
SongXin HVAC (manufacturing since 2009, 40+ export countries) is a water-cooled chiller supplier for industrial process cooling and commercial HVAC. The water-cooled screw chiller range covers 190–3600 kW with screw compressors (fixed-speed or inverter), flooded or falling-film evaporators, refrigerants R134a, R407C, R513A or R1234ze, −20 to +55°C ambient range, and 380/400/415V 3Ph 50/60Hz supply. The centrifugal water-cooled chiller range covers 350–2000 kW with centrifugal compressors (fixed or variable speed), shell-and-tube heat exchangers, peak COP up to 6.6 kW/kW, and low or medium-voltage supply (380/6000/10000V). Selection depends on cooling load, chilled-water supply/return temperature, condenser-water entering/leaving temperature, water flows, compressor type, cooling tower conditions, part-load profile, power supply, controls and maintenance plan. A quick evaporator-side check: Cooling kW = chilled-water flow m³/h × ΔT°C × 1.163. Units are ISO 9001, ISO 14001, CE, AHRI, RoHS and 3C certified.
02

What Is a Water-Cooled Chiller?

SongXin water-cooled screw chiller industrial plant

A water-cooled chiller produces chilled water by removing heat from a water loop and rejecting that heat to a condenser-water system. The condenser water usually flows to a cooling tower, where heat is rejected to outdoor air. The chilled water is then circulated to air handling units, fan coil units, process equipment or other cooling loads.

Water-cooled chillers are used in central plants where efficiency, stable operation and large capacity matter. SongXin states up to 30% energy savings versus air-cooled systems under favorable conditions, because water rejects heat more effectively than air — though this advantage depends on cooling tower performance and condenser-water temperature.

03

SongXin Water-Cooled Chiller Range

Chiller TypeCapacityBest ForKey Feature
Water-cooled screw chiller 190–3600 kW Medium to large commercial and industrial cooling Fixed-speed or inverter screw; flooded or falling-film evaporator
Centrifugal water-cooled chiller 350–2000 kW Very large central HVAC plants High efficiency at scale; peak COP up to 6.6 kW/kW
Dynamic gas/air-bearing centrifugal chiller Large central plants Lifecycle energy-critical applications Oil-free bearing technology; high part-load efficiency
Multiple-chiller staging (N+1) Any capacity via parallel units Hospitals, process cooling, phased or critical facilities Redundancy and staged part-load operation

For projects where water or tower maintenance is difficult, SongXin also supplies air-cooled screw chillers as an alternative.

04

Water-Cooled Screw Chiller Specifications

SongXin water-cooled screw chiller detail view
ParameterSpecification
Cooling capacity190–3600 kW
CompressorScrew, fixed-speed or inverter
EvaporatorFlooded type or falling-film type
RefrigerantsR134a, R407C, R513A, R1234ze (low-GWP available)
Ambient range−20°C to +55°C
Power supply380 / 400 / 415V, 3Ph, 50/60Hz (customisable)
NoiseLow-noise design, tested per ISO 3744
ControlsMicroprocessor controller, BMS-ready

The wide 190–3600 kW range covers a single hotel or factory plant up to mega-scale district cooling. Inverter-driven models improve part-load efficiency. Falling-film evaporators can raise efficiency at large capacities versus flooded designs.

05

Centrifugal Water-Cooled Chiller Specifications

ParameterSpecification
Cooling capacity350–2000 kW
CompressorCentrifugal, fixed-speed or variable-speed
Heat exchangerHigh-efficiency shell-and-tube
RefrigerantsR134a or low-GWP options (customisable)
Peak COPUp to 6.6 kW/kW (at favorable conditions)
Power supply3Ph, 380 / 6000 / 10000V, 50Hz
Design lifeOver 50,000 hours

Centrifugal units suit very large central plants — office towers, malls, hospitals, airports and district cooling. Medium-voltage options (6000/10000V) matter for large facilities with high-voltage distribution. Variable-speed centrifugal compressors significantly improve part-load efficiency. The 6.6 kW/kW COP is a peak value at favorable conditions; SongXin provides full-load and part-load performance at the project rating point on request.

For oil-free, high part-load efficiency applications, SongXin’s dynamic air-bearing centrifugal chiller uses oil-free bearing technology for even lower lifecycle energy costs.

06

Where Water-Cooled Chillers Are Used

Projects with long operating hours and strong, stable cooling demand benefit most from a water-cooled chiller plant:

SongXin water-cooled chiller for hotel and resort central plant
Hotels & Resorts
SongXin water-cooled screw chiller for office tower HVAC plant
Office Towers & Malls
SongXin centrifugal water-cooled chiller for hospital central cooling
Hospitals & Healthcare
Industrial manufacturing process cooling
Industrial & Process
Technicians maintaining central cooling equipment for data center HVAC
Data Centers
SongXin water-cooled chiller detail for airport or district cooling plant
Airports & District Cooling
07

Water-Cooled Chiller vs Air-Cooled Chiller

FactorWater-Cooled ChillerAir-Cooled Chiller
Heat rejection Cooling tower and condenser-water loop Outdoor air through condenser fans
Efficiency Often stronger for large stable loads (up to ~30% savings) Practical where water or tower maintenance is difficult
Installation Requires plant coordination and tower space Outdoor installation is often simpler
Maintenance Requires tower, condenser water and water treatment Less water-side maintenance
Best use Large buildings, central plants, industrial cooling Medium loads, equipment yards, water-limited sites
Key risk Poor water treatment, tower sizing or condenser-water temperature High-ambient derating and airflow recirculation

The best choice depends on local climate, water availability, operating hours, maintenance resources and total lifecycle cost. See also: SongXin air-cooled screw chiller.

08

Engineering Selection Workflow

See the full comparison at Air-Cooled vs Water-Cooled Screw Chillers. The key selection steps are:

  1. Confirm cooling duty. For comfort cooling, use the building load calculation; for process cooling, use the process heat load, required fluid temperature and operating hours.
  2. Confirm chilled-water temperature. Comfort systems often use ~7/12°C, but process cooling may need different conditions. Lower chilled-water temperatures reduce efficiency and may require special selection.
  3. Confirm condenser-water conditions. This is one of the most important inputs. If the cooling tower cannot deliver the assumed water temperature, the chiller loses capacity or consumes more energy.
  4. Review part-load operation. Most buildings run below full load most of the time. Inverter screw and variable-speed centrifugal units improve real annual energy use.
  5. Coordinate the full plant. The chiller must be matched with pumps, cooling towers, AHUs, FCUs, pipe sizing, valves, controls and water treatment.
09

Engineering Capacity and Flow Calculations

A serious water-cooled chiller quotation should include a basic water-side calculation:

FormulaUse
Cooling kW = flow m³/h × ΔT°C × 1.163 Checks evaporator-side cooling transfer
Flow m³/h = kW ÷ (1.163 × ΔT°C) Estimates required chilled-water flow
RT = kW ÷ 3.517 Converts kW to refrigeration tons
Heat rejection ≈ cooling kW + compressor power Helps size the cooling tower and condenser-water loop
Worked example: A Southeast Asian manufacturing plant used 600 TR (~2110 kW) of process cooling split across two chillers. At a 5°C chilled-water ΔT, the estimated chilled-water flow is 2110 ÷ (1.163 × 5) ≈ 363 m³/h. If the design changed to a 4°C ΔT, required flow would rise to ~453 m³/h — directly affecting pump size, pipe size, balancing and pressure drop. The condenser-water side must also be checked, because a chiller with poor condenser-water temperature loses efficiency regardless of a low purchase price.
10

Condenser-Water Temperature and Efficiency Logic

Cooling tower condenser water system maintenance

Water-cooled chillers are sensitive to condenser-water temperature. Lower entering condenser-water temperature improves efficiency because the compressor works against a lower condensing pressure; higher temperature increases compressor lift and energy use. Cooling tower performance depends on local wet-bulb temperature, tower sizing, airflow, water flow and maintenance.

A chiller rated at an optimistic condenser-water condition can look efficient on paper but underperform in hot, humid climates such as the Middle East, Africa and Southeast Asia. For fair comparison, ask each supplier to state the same rating conditions — a unit rated at 30°C entering condenser water cannot be compared directly with one rated at 32°C.

SongXin provides performance at your actual condenser-water condition rather than only at a nominal point.

11

Procurement Risks in Water-Cooled Chiller Projects

  • Ignoring cooling tower conditions. An undersized or poorly maintained tower means the chiller never reaches its rated performance.
  • Comparing only nominal capacity. Two chillers with the same nominal kW can differ significantly under real chilled and condenser-water conditions.
  • No water treatment plan. Scaling, fouling and corrosion reduce heat transfer, raise compressor power and shorten life.
  • No part-load strategy. Large plants run mostly at partial load; without staging and proper control, energy use is higher than expected.
  • Treating process cooling like comfort cooling. Industrial process loads need tighter temperature stability, longer hours, backup capacity and special fluid conditions.
12

Why Choose SongXin as Your Water-Cooled Chiller Supplier

SongXin has manufactured commercial and industrial HVAC equipment since 2009, with multiple production bases, national-level testing laboratories (verified from −40°C to +55°C) and more than 100 patents.

Certified Compliance

ISO 9001:2015, ISO 14001:2015, CE, AHRI, RoHS and 3C, with test reports and traceability for tender and project approval.

100% Factory Testing

Full performance verification, pressure and leak testing, and noise testing per ISO 3744 before every shipment.

Refrigerant Flexibility

Standard R134a and R407C plus low-GWP R513A and R1234ze, helping buyers meet F-gas and import regulations.

Customisation

Capacity, compressor type (fixed or inverter/variable), evaporator type, voltage (including medium voltage) and controls tailored per project.

Engineering Support

Free pre-sales selection, CAD drawings, full-load and part-load data, and project design and installation guidance.

Global Export Ready

EXW, FOB, CIF and DDP terms; full export documentation; service partners in major global markets.

ISO 9001:2015 ISO 14001:2015 CE AHRI RoHS 3C
13

Export and Logistics for Overseas Buyers

ItemDetail
Power supply380/400/415V 3Ph 50/60Hz standard; 6000/10000V medium voltage for large centrifugal plants
Trade termsEXW, FOB, CIF and DDP
Lead timeConfirmed per project — large custom chillers are production-scheduled at order
PaymentT/T, L/C, or Western Union for small orders; typically 30% deposit, 70% balance before shipment
DocumentationTest reports, compliance records and serial traceability for customs and approvals
Local supportService partners in major global markets for installation and after-sales
14

Project Case Study

Manufacturing plant process cooling plant Southeast Asia
600 TR Process Cooling · Southeast Asia

Manufacturing Plant — Two Water-Cooled Chillers + Pump Station

SongXin supplied two water-cooled chillers totaling 600 TR (~2110 kW) with a hydronic pump station for a manufacturing plant in Southeast Asia. The brief prioritised higher efficiency under peak load and a simplified maintenance plan.

Commissioning was supported with full test reports, which helped the plant verify performance and pass internal approvals. The two-chiller arrangement also provided staging flexibility and partial backup for continuous production.

15

Plant-Level RFQ Specification

For a professional RFQ, define the chiller and plant boundary clearly. A complete specification should state:

  • Scope: chiller only, chiller plus pumps, or full plant
  • Rated chilled-water and condenser-water temperatures
  • Required actual capacity at project condition
  • Full-load and part-load efficiency (IPLV or NPLV)
  • Compressor type and refrigerant preference (include F-gas or import regulation)
  • Evaporator and condenser type, pressure rating and allowable pressure drop
  • Controls and BMS protocol (Modbus, BACnet, LonWorks, etc.)
  • Protection functions: flow switch, freeze protection, high/low pressure, overload
  • Factory testing requirements and documentation scope

Clear RFQ language filters out quotations that omit critical conditions or scope, preventing apparent cost differences that disappear at delivery.

16

Frequently Asked Questions

SongXin water-cooled screw chillers cover 190–3600 kW, and centrifugal water-cooled chillers cover 350–2000 kW. Multiple units can be staged in parallel for larger plants or N+1 redundancy.
Screw chillers can use R134a, R407C, R513A or R1234ze, including low-GWP options to meet F-gas and import regulations. Centrifugal units use R134a or low-GWP options. The choice is confirmed per project and destination market.
Usually yes. A water-cooled chiller rejects heat to a condenser-water loop, and that heat is normally rejected outdoors through a cooling tower. Tower performance directly affects the chiller’s real efficiency and capacity.
Standard supply is 380/400/415V, 3Ph, 50/60Hz. For large centrifugal plants, medium-voltage options of 6000V and 10000V are available. Confirm your project’s electrical supply when requesting a quotation.
Yes. SongXin has supplied process cooling plants such as a 600 TR two-chiller installation in Southeast Asia. Process selection should confirm required fluid temperature, heat load, stability, operating hours, backup requirement and water quality.
Selecting without confirming condenser-water temperature, cooling tower performance and water quality. These conditions strongly affect real performance, so SongXin rates units at the project’s actual condenser-water condition.
17

Standards and Review Notes

Author: SongXin HVAC engineering content team. Updated: July 1, 2026. Technical review: water-cooled chiller sizing, plant RFQ conditions and export documentation reviewed by SongXin HVAC application engineering.

Chiller capacity and efficiency change with chilled-water temperature, condenser-water temperature, flow rate, fouling allowance and part-load profile. Use the values on this page as procurement guidance, then request a project-rated performance table for the final submittal.

SongXin HVAC Equipment Co., Ltd. is a global manufacturer of commercial and industrial HVAC systems, manufacturing since 2009 and supplying projects in 40+ countries. The range covers water-cooled screw and centrifugal chillers, air-cooled screw chillers, oil-free centrifugal chillers, air handling units, fan coil units, heat pumps, DX and VRF systems and precision cooling.

SongXin supports buyers with selection data, engineering discussion, certification documents, export packing and delivery coordination.

ISO 9001:2015 ISO 14001:2015 CE AHRI RoHS 3C 100% Factory Tested

Request Water-Cooled Chiller Selection

Send your cooling capacity, chilled-water and condenser-water temperatures, tower data and application. SongXin will review the working conditions and recommend a suitable water-cooled chiller within 24 hours.

Quick start: Not ready for a full RFQ? Just send three things — project location, application (e.g. hotel, factory, data center), and approximate cooling capacity in kW or TR.

Quotation note: Prices are project-based and confirmed after SongXin reviews capacity, chilled-water and condenser-water conditions, compressor type, quantity, destination and documentation requirements.

Get in Touch