SongXin HVAC is a Chinese fan coil unit manufacturer and supplier for commercial buildings, hotels, offices, apartments, hospitals, schools and retail projects worldwide. Manufacturing since 2009 and shipping to 40+ countries, SongXin produces cassette, concealed and exposed fan coil units that share one chilled-water coil platform, with a published range of 340–2380 m³/h airflow and 1.8–12.85 kW cooling capacity.
A fan coil unit (FCU) is a room or zone terminal unit that cools or heats air by passing it through a water coil. As an FCU supplier, SongXin helps buyers select by cooling capacity, airflow, water temperature, sound level, drainage, installation space, maintenance access and control method — not only by model name.
SongXin units are factory tested (100% leak and pressure testing) and backed by ISO 9001, ISO 14001, CE, AHRI, RoHS and 3C certification.
Quick Answer for Buyers
SongXin supplies three FCU types from the same coil family: cassette fan coil units (FP-KM series, 340–1360 m³/h, 1.9–7.8 kW cooling) for rooms with suspended ceilings; concealed fan coil units (340–2380 m³/h, 1.8–12.85 kW, 2-pipe or 4-pipe) for hidden ceiling-void installation; and exposed fan coil units for limited-ceiling and retrofit projects. Units run on 220V/1Ph/50Hz as standard.
For a reliable quotation, send room area or cooling load, chilled-water supply/return temperature, installation type, ceiling condition, airflow requirement, noise limit, voltage and project quantity. SongXin returns a selection at the project condition — usually within 24 hours.
What Is a Fan Coil Unit?
A fan coil unit is an HVAC terminal unit that uses a fan and a heat-exchange coil to condition indoor air. Chilled water or hot water flows through the coil, the fan moves room air across it, and conditioned air is supplied back into the room or zone.
Fan coil units are commonly connected to a central chilled-water system fed by an air-cooled or water-cooled chiller, heat pump or central plant. In many commercial buildings, AHUs handle fresh air and large ventilation loads while FCUs handle local zone cooling and heating.
SongXin Fan Coil Unit Range at a Glance
| FCU Type | Airflow | Cooling Capacity | Heating Capacity | Noise | Best For |
|---|---|---|---|---|---|
| Cassette (FP-KM) | 340–1360 m³/h | 1.9–7.8 kW | 2.8–10.5 kW | ≤38–47 dB(A) | Offices, hotel rooms, meeting rooms, retail with suspended ceilings |
| Concealed (horiz./vert., ducted) | 340–2380 m³/h | 1.8–12.85 kW | 2.7–18 kW | 37–54 dB(A) | Hotels, apartments, premium offices, hidden ceiling-void installation |
| Exposed (horiz./vert.) | 340–2380 m³/h | 1.8–12.85 kW | 2.7–18 kW | 37–54 dB(A) | Retrofits, schools, clinics, limited or no ceiling space |
Cooling capacities rated at 7°C chilled-water inlet; heating at 60°C hot-water inlet. Final capacity should always be confirmed at the project’s actual water and entering-air conditions.
SongXin Cassette Fan Coil Unit — FP-KM Series
The cassette range is ceiling-mounted with a decorative panel and 360-degree air supply, making it suitable for rooms with finished suspended ceilings. SongXin states up to 15% higher heat-transfer efficiency than conventional cassette coils, and the range is rated for a typical coverage of roughly 50–200 m² depending on load and ceiling height.
Before selecting a cassette unit, verify ceiling void depth, condensate pump requirement, panel dimensions and air throw.
| Model | Air Volume (m³/h) | Cooling (W) | Heating (W) | Noise | Power Supply |
|---|---|---|---|---|---|
| FP-KM-34 | 340 | 1900–2200 | 2800–3200 | ≤38 dB(A) | 220V/50Hz |
| FP-KM-51 | 510 | 2800–3300 | 4000–4600 | ≤40 dB(A) | 220V/50Hz |
| FP-KM-68 | 680 | 3700–4200 | 5200–5800 | ≤42 dB(A) | 220V/50Hz |
| FP-KM-85 | 850 | 4500–5000 | 6000–6800 | ≤43 dB(A) | 220V/50Hz |
| FP-KM-102 | 1020 | 5200–5800 | 7000–7800 | ≤45 dB(A) | 220V/50Hz |
| FP-KM-136 | 1360 | 7000–7800 | 9500–10500 | ≤47 dB(A) | 220V/50Hz |
Cooling/heating figures are nominal ranges across fan speeds. Lower noise = low-speed operation — the recommended design point for hotels and quiet spaces.
SongXin Concealed Fan Coil Unit
Concealed units are installed above the ceiling and connected to grilles or short ductwork, so only the supply and return grilles are visible. The range covers 340–2380 m³/h and 1.8–12.85 kW cooling, with input power from 36 to 291 W and water flow from 0.31 to 2.17 m³/h. Unit weight is 10.5–30 kg.
Available options for concealed units:
- Brushless DC (EC) motor — stepless speed control, lower energy use, quieter part-load.
- 2-way or 3-way water valve with electric actuator for automatic modulation.
- High-efficiency HEPA filtration — PM2.5 capture where IAQ is a priority.
Key selection points: available external static pressure at design airflow, access-panel location, return-air path, filter maintenance and condensate drain slope.
SongXin Exposed Fan Coil Unit
Exposed units share the 340–2380 m³/h / 1.8–12.85 kW platform but remain visible, mounted on the wall, floor or ceiling surface in horizontal or vertical orientation. Horizontal exposed units are typically installed 2.3–2.8 m above the floor.
They are the practical choice for renovation projects, schools, clinics and buildings without ceiling voids, because installation is faster and all components are accessible for service without removing ceiling panels.
Exposed units support 2-pipe (cooling-only or change-over) and 4-pipe (simultaneous cooling and heating) circuits and are available with brushless DC (EC) motors for reduced energy consumption.
Where Fan Coil Units Are Used
Fan coil units are widely used in commercial and light-industrial HVAC systems where each room or zone needs individual temperature control. In most projects, the AHU treats fresh air while FCUs handle local comfort.
Cassette, Concealed or Exposed: Which FCU Should You Choose?
Choose a cassette unit when the room has a suspended ceiling and the design allows a visible ceiling panel with broad multi-direction air distribution. Choose a concealed unit when the indoor equipment must be hidden above the ceiling and connected to grilles or short ducts — but confirm available static pressure and access panels first. Choose an exposed unit when ceiling space is limited, installation must be simple, or maintenance access matters more than hidden appearance.
For current product details, see SongXin’s terminal unit range, including cassette, concealed and exposed fan coil units.
Key Selection Data for a Fan Coil Unit
| Selection Item | Why It Matters |
|---|---|
| Room cooling load | Determines unit capacity and model size |
| Chilled-water temperature | Affects real cooling capacity and coil performance |
| Airflow requirement | Affects comfort, air distribution and noise |
| Installation type | Decides cassette, concealed, exposed or vertical model |
| Ceiling space | Important for concealed and cassette units |
| Noise limit | Critical for hotels, offices, apartments and hospitals |
| Condensate drainage | Prevents water leakage and ceiling damage |
| Control method | Determines thermostat, valve, BMS or centralised control |
| Voltage and frequency | Ensures electrical compatibility (220V/50Hz standard) |
| Quantity and room schedule | Helps optimise procurement and delivery planning |
Engineering Capacity Check for Fan Coil Units
A professional FCU quotation checks cooling capacity at the real project condition, not only at a catalogue rating point. Actual output changes with entering-air temperature, relative humidity, chilled-water supply temperature, water flow, fan speed and coil cleanliness. SongXin rates its FCU cooling at a 7°C chilled-water inlet; if your project uses a different supply temperature, delivered capacity will differ.
For chilled-water projects, a simple water-side check can be used at early stage:
| Formula | Meaning |
|---|---|
| Cooling kW = flow m³/h × ΔT°C × 1.163 | Quick estimate of water-side cooling transfer |
| Flow m³/h = kW ÷ (1.163 × ΔT°C) | Quick estimate of required FCU water flow |
| 1 RT = ~3.517 kW | Useful for converting buyer requirements in refrigeration tons |
Example: An FP-KM-34 is rated ~1.9–2.2 kW cooling. With a 5°C chilled-water ΔT, approximate water flow = 2.0 ÷ (1.163 × 5) ≈ 0.34 m³/h — consistent with published water-flow range for small units. This is only an early check; final selection uses the performance table at real entering-air and water conditions.
The supplier should clarify whether the listed capacity is total cooling, sensible cooling or heating. In humid climates the sensible heat ratio matters, because a unit that meets total capacity may still leave the room too humid.
Air-Side and Water-Side Coordination
Airflow and air throw decide whether the room feels comfortable after installation. Too much airflow can be noisy or drafty; too little leads to slow, uneven cooling. For concealed ducted units, confirm available external static pressure at the selected airflow.
On the water side, FCUs are part of a chilled-water loop and must be coordinated with the chiller capacity, pump flow, pipe sizing, balancing valves and control valves. Key items to confirm:
- Chilled-water supply/return temperature and total FCU water flow
- Coil and valve pressure drop; 2-pipe or 4-pipe design
- Valve control type and condensate drain routing
- Pump sizing — ignoring FCU pressure drop can lead to an undersized pump
- Balancing — ignored balancing creates uneven cooling, even when the model is correct
Procurement Risks When Buying Fan Coil Units
-
Buying by nominal capacity only. Capacity changes with water temperature, entering air, airflow and coil design. A catalogue number does not guarantee room comfort.
-
Ignoring noise. Noise is the most common comfort complaint in hotels and bedrooms. Compare sound level at the fan speed likely to run in service, not at maximum airflow.
-
Poor condensate drainage. Wrong drain slope, blocked lines or missing pumps cause ceiling damage — especially with concealed and cassette units.
-
Not confirming external static pressure. Ducted concealed units need enough ESP, or airflow will be weak after installation.
-
No maintenance access. Filters, coils, valves and drain pans need service space; hidden units without access panels become expensive to maintain.
Why Choose SongXin as Your Fan Coil Unit Supplier
SongXin has manufactured commercial and industrial HVAC equipment since 2009, with multiple production bases, national-level testing laboratories (verified from −40°C to +55°C) and more than 100 patents. For buyers, this translates into verifiable quality:
ISO 9001:2015, ISO 14001:2015, CE, AHRI, RoHS and 3C, with test reports and traceability for tender and project approval.
Leak testing on critical circuits, pressure testing above 1.6 MPa, acoustic validation and long-run reliability simulation.
Free pre-sales selection, CAD drawings, water and air-side data, and a typical 24-hour response to technical inquiries.
Multiple coil rows, motor types (including EC), valve packages, controls and OEM/ODM branding available.
5-year warranty on cassette FCUs, with spare-parts supply and after-sales support included.
EXW, FOB, CIF and DDP terms; export-standard cartons and pallets; full documentation for customs and approvals.
Export and Logistics for Overseas Buyers
| Item | Detail |
|---|---|
| Standard voltage | 220V/1Ph/50Hz; other voltages/frequencies available for export markets |
| Trade terms | EXW, FOB, CIF and DDP |
| Lead time | 7–15 working days for standard orders |
| Packaging | Reinforced export-standard cartons and pallets for long-distance transit |
| Payment | T/T, L/C, or Western Union for small orders; typically 30% deposit, 70% balance before shipment |
| Documentation | Test reports, compliance records and serial traceability for customs and approvals |
For humid climates such as the Middle East, Africa and Southeast Asia, SongXin also advises on drain-pan insulation, pipe insulation and low-speed selection to control condensation and noise.
Project Case Study
Luxury Hotel Renovation — Fan Coil Units + Fresh Air System
SongXin supplied fan coil units integrated with a fresh-air system for a luxury hotel renovation in Africa covering 260 guest rooms. The brief prioritised low-noise comfort and minimal disruption to occupied floors.
Units were selected to meet room loads at low-to-medium fan speed for quiet operation, improving indoor air quality while keeping the renovation phased and on schedule.
Quality Evidence and Documents SongXin Provides
Professional buyers should expect documents that make a quotation verifiable. SongXin can provide:
Installation and Commissioning Checks
Many FCU failures come from installation, not factory quality. Before handover:
- Confirm model and orientation; check chilled-water connections and flush pipework
- Confirm water flow and valve operation
- Verify condensate drain slope and pump operation if used
- Clean the filter before testing; measure supply-air temperature at a typical operating condition
- Confirm fan-speed and thermostat response; inspect for vibration, abnormal noise and leakage
- For multi-room projects, sample rooms near and far from the pump, on different floors and with different solar exposure
Frequently Asked Questions
Standards and Review Notes
Author: SongXin HVAC engineering content team. Updated: July 1, 2026. Technical review: fan coil unit selection and export documentation reviewed by SongXin HVAC application engineering.
Published FCU capacity, airflow, water-temperature and sound discussions should be checked against the project selection table before procurement. The external standards below are used as engineering references; project compliance still depends on the local code, tender specification and final approved submittal.
- AHRI 440/441 for fan-coil performance rating terminology and published-rating context.
- ANSI/ASHRAE Standard 62.1 for ventilation and indoor-air-quality design context in commercial buildings.
- SongXin certification and compliance records for company-level ISO, CE, AHRI, RoHS and 3C evidence used on this page.
SongXin HVAC Equipment Co., Ltd. is a global manufacturer of commercial and industrial HVAC systems, manufacturing since 2009 and supplying projects in 40+ countries. The product range covers fan coil units, air handling units, air-cooled and water-cooled chillers, heat pumps, DX and VRF systems and precision cooling.
SongXin supports project buyers with equipment selection, technical data, certification documents, export packing and coordinated delivery.
Request Fan Coil Unit Selection
Send your room schedule, chilled-water conditions, installation type and quantity. SongXin will recommend cassette, concealed or exposed fan coil units and reply within 24 hours.
Quick start: Not ready for a full RFQ? Just send three things — project location, building type, and approximate cooling load or room count.
Quotation note: Prices are project-based and confirmed after SongXin reviews the room schedule, unit type, quantity, voltage, controls, destination and documentation requirements.
Get in Touch