50 Ton Chiller Selection

50 Ton Air-Cooled Screw Chiller Selection Guide for Commercial HVAC Projects

A 50 ton air-cooled screw chiller is often used in commercial buildings, industrial facilities and process cooling projects that need reliable chilled water without a cooling tower. This guide explains how to check real capacity, water conditions, ambient temperature and supplier data before buying.

50 ton air cooled screw chiller for commercial HVAC project
50 RT is about 176 kWNo cooling tower

Choosing a 50 ton chiller is not as simple as matching a number on a quotation sheet. The real performance depends on chilled-water temperature, outdoor ambient temperature, water flow, refrigerant circuit design, compressor performance, installation conditions and controls.

For commercial HVAC, a 50 ton air-cooled screw chiller may serve AHUs, fan coil units or medium-size chilled-water systems. For industrial process cooling, the buyer must also confirm temperature stability, fluid type, operating hours and backup requirements.

Direct Answer

A 50 ton air-cooled screw chiller provides about 176 kW of cooling capacity under standard conversion, but the actual usable capacity depends on chilled-water temperature, outdoor ambient temperature, water flow, installation airflow and manufacturer rating conditions.

Buyers should not purchase a 50 ton chiller only by nominal capacity. They should confirm the real performance at the project location and operating conditions. For a broader product range, see SongXin’s air-cooled screw chiller line.

What Does 50 Ton Mean?

In HVAC, one refrigeration ton is commonly understood as about 3.517 kW of cooling capacity. A 50 ton chiller is therefore approximately 176 kW of cooling capacity under rated conditions. But rated conditions are not always the same as your project conditions.

1 RTAbout 3.517 kW cooling capacity
50 RTAbout 175.85 kW at standard conversion
Real DutyMust be checked at project ambient and water temperature

When Is a 50 Ton Air-Cooled Screw Chiller Used?

Commercial building using air cooled screw chiller

Commercial HVAC

Offices, small hotels, retail buildings, showrooms, schools, clinics and public buildings.

Industrial process cooling application for 50 ton chiller

Industrial Process Cooling

Process water cooling, equipment cooling, workshop air conditioning or production support.

Technical room and laboratory cooling with chilled water

Technical Spaces

Electrical rooms, laboratories, control rooms or other technical zones with air-side cooling equipment.

Air cooled screw chiller retrofit replacement project

Retrofit Projects

Air-cooled chillers can simplify replacement because they do not require a cooling tower.

Commercial HVAC vs Process Cooling Use

ItemCommercial HVACIndustrial Process Cooling
Typical purposeComfort cooling for buildingsCooling machines, production lines or process water
Load profileChanges by occupancy and scheduleMay be continuous or production-based
Water temperatureOften standard chilled-water rangeMay require custom water temperature
Control focusComfort, energy saving and BMSTemperature stability and equipment protection
Risk if undersizedPoor comfortProduction interruption or equipment alarm
Data requiredBuilding load, AHU/FCU data, scheduleProcess heat load, flow, temperature range, fluid type

Why Choose an Air-Cooled Screw Chiller?

  • No cooling tower, condenser water pump or tower water treatment
  • Outdoor installation on roof, ground platform or equipment yard
  • Screw compressor design for medium and larger cooling loads
  • Practical for water-limited projects or retrofit replacement
  • Works with AHUs, fan coil units and selected process cooling systems
  • Simpler plant layout than water-cooled systems in many projects

50 Ton Chiller Selection Checklist

Selection ItemExample Question
Cooling capacityIs 50 ton based on load calculation or estimate?
Leaving water temperatureDo you need 7 deg C, 10 deg C, 12 deg C or another value?
Water flow rateIs the pump flow confirmed?
Outdoor ambient temperatureWhat is the design temperature in summer?
Power supplyWhat voltage, phase and frequency are available?
ApplicationComfort cooling or process cooling?
Installation locationRoof, ground, platform or equipment yard?
Airflow clearanceIs there enough space around the condenser?
Noise limitAre there nearby offices, hotels or residential areas?
ControlsIs BMS or remote monitoring required?

Rated Tons Are Only the Starting Point

A 50 ton air-cooled screw chiller selected for a mild climate may not deliver the same performance in a very hot region unless the condenser and compressor are configured for that condition.

For a deeper method, read SongXin’s guide on how to select an air-cooled chiller for commercial HVAC projects.

Outdoor air cooled screw chiller installation and condenser airflow

Technical Datasheet Items to Request

  • Rated cooling capacity and rating condition
  • Capacity at your outdoor design temperature
  • Input power and efficiency data
  • Compressor type and quantity
  • Refrigerant
  • Evaporator type
  • Water pressure drop and recommended water flow
  • Operating ambient temperature range
  • Sound level, dimensions and operating weight
  • Electrical data and starting method
  • Control interface and protection functions
  • Shipping dimensions and documentation

Chilled-Water Temperature and Outdoor Ambient Matter

Water-Side Conditions

  • Leaving chilled-water temperature
  • Entering chilled-water temperature
  • Required water flow
  • Water-side pressure drop
  • Glycol use for freezing protection or process reasons

Outdoor Conditions

  • Maximum summer design temperature
  • Condenser coil design
  • Fan capacity
  • High-pressure protection
  • Installation airflow clearance

Installation Space and Airflow

Poor installation can reduce chiller performance. An air-cooled chiller needs enough open space for condenser air intake and hot air discharge. The supplier should provide installation clearance recommendations before ordering.

  • Avoid installing units too close to walls
  • Do not block condenser airflow
  • Avoid heat recirculation zones
  • Keep enough service access
  • Separate multiple units correctly
  • Prevent hot discharge air from returning to the condenser

Air-Cooled Screw Chiller vs Scroll Chiller at 50 Ton

ItemAir-Cooled Screw ChillerAir-Cooled Scroll Chiller
Compressor typeScrew compressorMultiple scroll compressors
Typical useMedium-load commercial and industrial systemsSmall to medium commercial systems
Part-load designDepends on compressor and control designOften staged by multiple compressors
MaintenanceRequires screw compressor service knowledgeModular compressor replacement may be easier
Best choice depends onLoad profile, project standard, budget and service planLoad profile, budget and maintenance preference

What Affects 50 Ton Chiller Price?

  • Compressor brand and configuration
  • Refrigerant
  • Heat exchanger design
  • Control system
  • Ambient temperature design
  • Noise treatment
  • Electrical components
  • Protection functions
  • Anti-corrosion options
  • Factory testing requirements
  • Shipping destination
  • Custom documentation needs

How to Compare 50 Ton Chiller Quotations

Quotation ItemSupplier ASupplier BSupplier C
Rated capacity condition
Actual capacity at project ambient
Leaving water temperature
Compressor type
Refrigerant
Noise level
BMS option
Factory testing
Warranty and support

Questions to Ask Your Chiller Supplier

  • What rating condition is the 50 ton capacity based on?
  • What is the capacity at my outdoor design temperature?
  • What is the recommended water flow?
  • What is the leaving chilled-water temperature range?
  • What compressor type is used?
  • What protection functions are included?
  • What is the noise level?
  • What installation clearance is required?
  • Can the unit connect to BMS?
  • What factory testing is available?

Common Mistakes When Buying a 50 Ton Chiller

  • Buying only by nominal tonnage
  • Ignoring local ambient temperature
  • Not checking water-side conditions
  • Underestimating startup current
  • Missing glycol requirements
  • Forgetting noise limits
  • Poor condenser airflow planning
  • Not confirming spare parts and service support
  • Comparing price without matching specifications
  • Not preparing load calculation data

When to Contact a Supplier

You can contact SongXin once you already know several core project conditions. Even if the final load calculation is not complete, early supplier feedback can help confirm whether a 50 ton air-cooled screw chiller is the right capacity range or whether a smaller or larger model should be reviewed.

  • Project location
  • Application type
  • Required capacity or estimated load
  • Chilled-water temperature
  • Outdoor design temperature
  • Power supply
  • Installation location
  • Required delivery time

Frequently Asked Questions

How many kW is a 50 ton chiller?

A 50 ton chiller is approximately 176 kW under standard conversion. Final rated capacity depends on the manufacturer and operating conditions.

Is a 50 ton air-cooled screw chiller suitable for commercial buildings?

Yes, it can be suitable for medium-size commercial buildings, support buildings and retrofit projects. A load calculation should confirm whether 50 ton is enough.

Does an air-cooled screw chiller need a cooling tower?

No. An air-cooled screw chiller rejects heat directly to outdoor air and does not require a cooling tower.

Can a 50 ton chiller be used for process cooling?

Yes, but process cooling requires careful confirmation of water temperature, flow rate, operating hours and temperature stability.

What should I check before buying?

Check cooling capacity at real conditions, water temperature, ambient temperature, power supply, installation clearance, controls, noise and supplier support.

Should I choose screw or scroll compressor at 50 ton?

Both can be considered depending on project requirements. Compare load profile, service preference, efficiency, budget and supplier support.

Where 50 Tons Sits in the SongXin Range

A 50 ton chiller, about 176 kW, sits at the lower end of SongXin’s air-cooled screw chiller line, which spans 173-1475 kW. If your load calculation lands a little above or below 50 tons, adjacent capacities can be reviewed instead of forcing the wrong size.

ItemSongXin Range
Cooling capacity173 – 1475 kW, about 49 – 419 RT
Cooling power input52 – 388 kW
Operating ambient-35 deg C to +48 deg C
Water flow30 – 236 m3/h
Water-side pressure drop<=60 – <=200 kPa
Compressor / condenserScrew compressor / air-cooled condenser, no cooling tower

About SongXin

SongXin (SXIN HVAC) is a commercial and industrial HVAC manufacturer with 15+ years of experience, 500+ delivered projects and customers in 50+ countries. It supplies air-cooled and water-cooled chillers, DX systems, heat pumps and air handling units with export packing and global delivery. Contact: info@sxinhvac.com · +86 153-1889-6990.